Troubleshooting Electrical controller

SC Series

1The LED display does not light up.
2No output even when the overcurrent setting is set to the minimum value.
3The output relay operates immediately after starting.
4The output relay operates due to a momentary overload during operation.
5The output relay does not operate when overloaded.

SB series, ED series

6MON (monitor lamp) does not light up. ---SB series
LED display does not light up. ---ED series
7No output even when the current volume setting is at minimum.
8The output relay operates immediately after starting.
9The output relay operates due to a momentary overload during operation.
10The output relay does not operate when overloaded.

150 Series

11The power indicator light does not light up.
12The % meter does not move while driving.
13The output relay operates immediately after starting.
14The motor starts, but the % meter reading is different from the actual current.
15The output relay operates due to a momentary overload during operation.
16The output relay does not operate when overloaded.

50 Series

17The input indicator light does not light up after the motor starts.
18The output relay operates immediately after starting.
19The output relay operates due to a momentary overload during operation.
20The output relay does not operate when overloaded.
回答へ

SC Series

1The LED display does not light up.
Inspection item 1 A1, A2 wiring Inspection results Not wired correctly Solution Wire correctly
Inspection item 2 Is the voltage of A1 and A2 between 100 and 240V? Inspection results It is different from the 100 to 240V range. Solution Between 100 and 240V
Return to list
2No output even when the overcurrent setting is set to the minimum value.
Inspection item 1 Wiring to current transformers (CTs) Inspection results Not wired correctly Solution Wire correctly
Inspection item 2 Shock Relay model number Inspection results Model number error Solution Replace with the correct one
Inspection item 3 TEST function Inspection results The output relay does not operate Solution Shock Relay Replacement
Return to list
3The output relay operates immediately after starting.
Inspection item 1 Start time setting Inspection results The setting is too short Solution Adjust to the appropriate value
Inspection item 2 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Inspection item 3 Setting parameters Inspection results Phase reversal, Open phase, and Phase unbalance are set to ON Solution Check for Phase reversal or Open phase phase wiring
Return to list
4The output relay operates due to a momentary overload during operation.
Inspection item 1 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too short Solution Adjust to the appropriate value
Return to list
5The output relay does not operate when overloaded.
Inspection item 1 Load Current Settings Inspection results Setting too high Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too long Solution Adjust to the appropriate value
Inspection item 3 TEST function Inspection results The output relay does not operate Solution Shock Relay Replacement
Return to list

SB series, ED series

6MON (monitor lamp) does not light up. ---SB series
LED display does not light up. ---ED series
Inspection item 1 A1, A2 wiring Inspection results Not wired correctly Solution Wire correctly
Inspection item 2 Is the voltage of A1 and A2 24 to 240VAC/DC? Inspection results It is different from 24 to 240V. Solution Between 24 and 240V
Return to list
7No output even when the current volume setting is at minimum.
Inspection item 1 Wiring to current transformers (CTs) Inspection results Not wired correctly. Solution Wire correctly
Inspection item 2 Shock Relay model number Inspection results Model number error Solution Replace with the correct one
Inspection item 3 Press the TEST button Inspection results The output relay does not operate Solution Shock Relay Replacement
Return to list
8The output relay operates immediately after starting.
Inspection item 1 Start time setting Inspection results The setting is too short Solution Adjust to the appropriate value
Inspection item 2 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Return to list
9The output relay operates due to a momentary overload during operation.
Inspection item 1 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too short Solution Adjust to the appropriate value
Return to list
10The output relay does not operate when overloaded.
Inspection item 1 Load Current Settings Inspection results Setting too high Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too long Solution Adjust to the appropriate value
Inspection item 3 Press the TEST button Inspection results The output relay does not operate Solution Shock Relay Replacement
Return to list

150 Series

11The power indicator light does not light up.
Inspection item 1 POWER terminal wiring Inspection results Not wired correctly Solution Wire correctly
Inspection item 2 POWER terminal voltage (between terminals 100/110V)
In case of the above operating power supply
Inspection results Different from AC100/110V Solution Switch to AC100/110V
Inspection item 3 POWER terminal voltage (between terminals 200/220V)
In case of the above operating power supply
Inspection results Different from AC200/220V Solution Set to AC200/220V
Return to list
12The % meter does not move while driving.
Inspection item 1 Current transformer wiring Inspection results Not wired correctly Solution Wire correctly
Inspection item 2 Current transformer model number Inspection results Model number error Solution Replace with the correct one
Inspection item 3 Press the TEST button Inspection results The % meter does not move Solution Shock Relay Replacement
Return to list
13The output relay operates immediately after starting.
Inspection item 1 Start time setting Inspection results The setting is too short Solution Adjust to the appropriate value
Inspection item 2 Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Return to list
14The motor starts, but the % meter reading is different from the actual current.
Inspection item 1 Common type current transformer Inspection results Terminals not wired correctly Solution Wire correctly
Inspection item 2 Through-type current transformer Inspection results The number of penetrations is incorrect Solution Correct penetration count
Inspection item 3 Current transformer model number Inspection results Model number error Solution Replace with the correct one
Return to list
15The output relay operates due to a momentary overload during operation.
Inspection item 1 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too short Solution Adjust to the appropriate value
Return to list
16The output relay does not operate when overloaded.
Inspection item 1 Load Current Settings Inspection results Setting too high Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too long Solution Adjust to the appropriate value
Inspection item 3 Press the TEST button Inspection results The output relay does not operate Solution Shock Relay Replacement
Return to list

50 Series

17The input indicator light does not light up after the motor starts.
Inspection item 1 POWER terminal wiring Inspection results Not wired correctly Solution Wire correctly
Inspection item 2 POWER terminal voltage (between terminals 100/110V)
In case of the above operating power supply
Inspection results Different from AC100/110V Solution Switch to AC100/110V
Inspection item 3 POWER terminal voltage (between terminals 200/220V)
In case of the above operating power supply
Inspection results Different from AC200/220V Solution Set to AC200/220V
Return to list
18The output relay operates immediately after starting.
Inspection item 1 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Return to list
19The output relay operates due to a momentary overload during operation.
Inspection item 1 Load Current Settings Inspection results Setting too low Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too short Solution Adjust to the appropriate value
Return to list
20The output relay does not operate when overloaded.
Inspection item 1 Load Current Settings Inspection results Setting too high Solution Adjust to the appropriate value
Inspection item 2 Shock Time Setting Inspection results The setting is too long Solution Adjust to the appropriate value
Inspection item 3 Current transformer model number Inspection results Model number error Solution Replace with the correct one
Return to list

*If the results of the above investigation show that there are no problems and that Shock Relay needs to be replaced, please contact our customer support center.